SDM-CD16D 16 Channel DigitalControl Port Expansion ModuleRevision: 8/07Copyright © 2000-2007Campbell Scientific, Inc.
SDM-CD16D 16 Channel Digital Control Port Expansion Module TABLE 2. Switch Position and Addresses Switch Setting Base 4 Address 0 00 1 01 2 02 3 03
SDM-CD16D 16 Channel Digital Control Port Expansion Module 6. Datalogger Instructions 6.1 CRBasic The SDMCD16AC instruction in CRBasic is used by ou
SDM-CD16D 16 Channel Digital Control Port Expansion Module Instruction 104 – SDM-CD16D used with CR10/10X, CR23X, CR7and 21X dataloggers Parameter Ty
SDM-CD16D 16 Channel Digital Control Port Expansion Module a data bit on C1 (LSB first) on the falling edge of the C2 clock. The SDM-CD16D shifts in t
SDM-CD16D 16 Channel Digital Control Port Expansion Module Cooling unit: Activate when temperature >27.5°C. Deactivate when temperature <24.5°C.
SDM-CD16D 16 Channel Digital Control Port Expansion Module 5: If (X<=>F) (P89) if the heater is on (heater 1: 10 -- X Loc [ Heat_1 ] co
SDM-CD16D 16 Channel Digital Control Port Expansion Module 16: If (X<=>F) (P89) check lower threshold to 1: 1 -- X Loc [ Temp_1 ] see
SDM-CD16D 16 Channel Digital Control Port Expansion Module 28: End (P95) end ‘then do/else’ 29: Do (P86) reset flag 1 1: 21 Set Flag
SDM-CD16D 16 Channel Digital Control Port Expansion Module *Table 3 Subroutines End Program -Input Locations-1 Temp_1 7 4 0 2 Temp_2 10 0 0 3 Temp_3
This is a blank page.
Warranty and Assistance The SDM-CD16D 16 CHANNEL DIGITAL CONTROL PORT EXPANSION MODULE is warranted by CAMPBELL SCIENTIFIC, INC. to be free from defec
Campbell Scientific Companies Campbell Scientific, Inc. (CSI) 815 West 1800 North Logan, Utah 84321 UNITED STATES www.campbellsci.com info@campbells
SDM-CD16D Table of Contents PDF viewers note: These page numbers refer to the printed version of this document. Use the Adobe Acrobat® bookmarks tab
This is a blank page.
SDM-CD16D 16 Channel Digital Control Port Expansion Module The SDM-CD16D (see Figure 1) is a synchronously addressed peripheral. It has 16 control por
SDM-CD16D 16 Channel Digital Control Port Expansion Module 2. Control Specifications 2.1 General Compatible dataloggers: CR800, CR850, CR1000, CR30
SDM-CD16D 16 Channel Digital Control Port Expansion Module 3. Power Considerations The SDM-CD16D power requirements are large compared to most Campbe
SDM-CD16D 16 Channel Digital Control Port Expansion Module 4. Installation For correct operation the SDM-CD16D must be installed where there is no ri
SDM-CD16D 16 Channel Digital Control Port Expansion Module Use a screwdriver in either the top or front slot, as appropriate, to open the terminal spr