Campbell-scientific SDM-SIO1 Serial Input/Output Module Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Matériel Campbell-scientific SDM-SIO1 Serial Input/Output Module. Campbell Scientific SDM-SIO1 Serial Input/Output Module User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer

Résumé du contenu

Page 1 - Input/Output Module

SDM-SIO1 SerialInput/Output ModuleRevision: 7/13 Copyright © 2008-2013Campbell Scientific, Inc.

Page 2

SDM-SIO1 Serial Input/Output Module 2.2.2 SDM-SIO1 Voltage Specifications Connection Minimum Voltage(1) Nominal Voltage(1) Maximum Voltage(1) Power

Page 3 - Warranty

SDM-SIO1 Serial Input/Output Module 2.3 Temperature and Humidity Ranges Temperature Range Minimum Maximum Notes Standard range –25ºC +50ºC Ext

Page 4 - Assistance

SDM-SIO1 Serial Input/Output Module TABLE 3-1. SDM Address Settings Rotary Switch Position SDM Address SerialOpen CommandComm. Port Number 0 0 32 1

Page 5 - Table of Contents

SDM-SIO1 Serial Input/Output Module TABLE 3-2. SDM-SIO1 Connections (left to right as viewed from the front of the unit) SDM Power Connections RS-2

Page 6

SDM-SIO1 Serial Input/Output Module As shown above in TABLE 3-3 connections 1 to 5 need to be made to the datalogger. SDM connections are made to appr

Page 7 - 1. Introduction

SDM-SIO1 Serial Input/Output Module 3.3 Examples for Connecting the SDM-SIO1 to Other Equipment 3.3.1 RS-485 One to One Connection Example 1 C1

Page 8 - 2. Specifications

SDM-SIO1 Serial Input/Output Module 3.3.2 RS-485 Multi Unit / In Line Example 1 C1 2 C2 RS-485 0V for ground referencing 3 C3

Page 9 - 2.2 Electrical Parameters

SDM-SIO1 Serial Input/Output Module 3.3.3 RS-485 Half Duplex Wiring Example 1 C1 2 C2 3 C3 To logger 4 G

Page 10 - 2.2.3 EMC Compliance

SDM-SIO1 Serial Input/Output Module 3.3.5 RS-232 Wiring Example with Handshaking 1 C1 2 C2 3 C3 To logger 4 G

Page 11 - 3. Installation

SDM-SIO1 Serial Input/Output Module 3.3.7 Connecting a 9-Way Socket to the SDM-SIO1 1 C1 2 C2 3 C3 To logger 4 G

Page 13

SDM-SIO1 Serial Input/Output Module sends data one-way to the datalogger, run the SDM-SIO1 in “receive only mode” as this does not turn on the output

Page 14 - 3.2 Safety Considerations

SDM-SIO1 Serial Input/Output Module TABLE 4-1. Communications Port Parameters RS-232 Code Parity No. Stop Bits No. Data Bits 0 None 1 8 1 Odd 1

Page 15 - Equipment

SDM-SIO1 Serial Input/Output Module TABLE 4-3. Communications Port Parameters RS-485 Half Duplex Code Parity No. Stop Bits No. Data Bits 48 None

Page 16

SDM-SIO1 Serial Input/Output Module 4.1.2 SerialClose() This will place the SDM-SIO1 unit into shutdown mode where only SDM communications will opera

Page 17

SDM-SIO1 Serial Input/Output Module 4.1.5 SerialInBlock() The SerialBlock() instruction can be used as described in the datalogger manual. However,

Page 18

SDM-SIO1 Serial Input/Output Module worth noting that normally setting the BaudRate to a negative number will enable automatic baud rate detection, th

Page 19 - 3.4 Power Conservation

SDM-SIO1 Serial Input/Output Module 4.3 Example Datalogger Programs Some simple examples of how to write programs in CRBasic to send and receive data

Page 20 - 4.1.1 SerialOpen()

SDM-SIO1 Serial Input/Output Module 4.3.2 Example Using RS-485 Mode '----------------------------------------------------------------------- &ap

Page 21

SDM-SIO1 Serial Input/Output Module 22 5. Firmware Upgrades and Flash Signature Errors 5.1 Upgrading the Firmware Firmware upgrades can be done by c

Page 22

Appendix A. Using the Handshaking Lines for General Input/Output This Appendix describes how to use the CTS and RTS lines for input and output ports

Page 23 - 4.1.4 SerialOut()

Warranty “PRODUCTS MANUFACTURED BY CAMPBELL SCIENTIFIC, INC. are warranted by Campbell Scientific, Inc. (“Campbell”) to be free from defects in materi

Page 24

Appendix A. Using the Handshaking Lines for General Input/Output ‘IF value returned is over 4095 then input line is high ‘ELSE input line must b

Page 25

Appendix A. Using the Handshaking Lines for General Input/Output Value of ‘SerialOutBlock’‘SerialExpression’ variable Voltage on the output line 1

Page 26

Appendix A. Using the Handshaking Lines for General Input/Output A-4

Page 28 - 5.1 Upgrading the Firmware

Campbell Scientific Companies Campbell Scientific, Inc. (CSI) 815 West 1800 North Logan, Utah 84321 UNITED STATES www.campbellsci.com • info@campbel

Page 29 - A.1 The Input Pin (Pin 8)

Assistance Products may not be returned without prior authorization. The following contact information is for US and international customers residing

Page 30 - A.2 The Output Pin (Pin 9)

Table of Contents PDF viewers: These page numbers refer to the printed version of this document. Use the PDF reader bookmarks tab for links to spec

Page 31

Table of Contents ii 4.3 Example Datalogger Programs... 20 4.3.1 Example Using RS-232 Mode...

Page 32

SDM-SIO1 Serial Input/Output Module The SDM-SIO1 Module is designed to allow expansion of the number of serial ports available on a datalogger for co

Page 33

SDM-SIO1 Serial Input/Output Module 2. Specifications 2.1 Supported Data Rates and Protocols Data rates and protocols are set up using the SerialOpe

Page 34

SDM-SIO1 Serial Input/Output Module 2.2 Electrical Parameters 2.2.1 SDM-SIO1 Current Consumption Nominal Max Notes General Currents Standby current