Campbell-scientific A6REL-12 Relay Driver Manuel d'utilisateur Page 9

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 12
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 8
A6REL-12 Relay Driver
5.1 CRBasic
Although the following example is a CR1000 program, other dataloggers that
use CRBasic such as the CR800 and CR3000 are programmed similarly.
'CR1000 Series Datalogger
'Declare Public Variables
Public PTemp, batt_volt, P, TC
'Define Data Tables
DataTable (Test,1,-1)
DataInterval (0,15,Sec,10)
Minimum (1,batt_volt,FP2,0,False)
Sample (1,PTemp,FP2)
Sample (1,TC,FP2)
EndTable
'Main Program
BeginProg
Scan (5,Sec,0,0)
Battery (Batt_volt)
'Measure TC reference temperature
PanelTemp (PTemp,250)
'Make temperature measurement and convert it to degrees Fahrenheit
TCDiff (TC,1,mV2_5C,1,TypeT,PTemp,True ,0,250,1.8,32)
'If temperature is greater than 99 set Port low
If TC>99 then
P=0
'If temperature is less than 96 set Port high
ElseIf TC<96 then
P=1
EndIf
PortSet (1 ,P)
'Call Output Tables
'Example:
CallTable Test
NextScan
EndProg
5
Vue de la page 8
1 2 3 4 5 6 7 8 9 10 11 12

Commentaires sur ces manuels

Pas de commentaire