Campbell-scientific NL100 Network Link Interface Manuel d'utilisateur Page 31

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 42
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 30
Appendix A. CS I/O Port
The CS I/O port is Campbell Scientific's input/output port. It is not a standard
RS-232 pin-out. The following table provides pin-out information on the port
when connected to a datalogger.
Pin
Name
Signal
Type
Description
1 5 V (supplied by the
datalogger)
Input Not used by NL100/105
2 Signal Ground Provides reference for voltage
levels
3 Ring Output Raised by a NL100/105 to put
the datalogger into the
telecommunications mode
4 RXD Output Serial data transmitted to the
datalogger
5 Modem Enable Input Raised by the datalogger when
it determines that the
NL100/105 raised the ring line
6 Synchronous Device
Enable
Input Used by the datalogger to
address the NL100/105 when
the NL100/105 is configured
as a synchronous device
7 Clock/Handshake Input Used by the datalogger with
SDE and TXD lines to address
and transfer data to
synchronous devices
8 12 V (supplied by the
datalogger)
Not used by the NL100/105
9 TXD Input Serial data received from the
datalogger
A-1
Vue de la page 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 41 42

Commentaires sur ces manuels

Pas de commentaire