DCP100 DATA COLLECTION PLATFORM
15
;{21X}
;
*Table 1 Program
01: 10.0 Execution Interval
(seconds)
;Measure reference temperature.
01: Internal Temperature (P17)
1: 1 Loc [ RefTemp ]
;Measure thermocouple temperature.
02: Thermocouple Temp (DIFF) (P14)
1: 1 Reps
2: 1 ± 5 mV Slow Range
3: 5 DIFF Channel
4: 1 Type T (Copper-Constantan)
5: 1 Ref Temp Loc [ RefTemp ]
6: 2 Loc [ TCDef_F ]
7: 1.8 Mult
8: 32 Offset
;Measure battery voltage every 10 seconds.
03: Batt Voltage (P10)
1: 3 Loc [ Battery ]
;Set Output Flag High (10) every hour
04: If time is (P92)
1: 0 Minutes into a
2: 60 Minute Interval
3: 10 Set Output Flag High
;Designate 111 as ID for hourly data
05: Set Active Storage Area (P80)
1: 1 Final Storage
2: 111 Array ID or Loc
[ _________ ]
;Timestamp data
06: Real Time (P77)
1: 220 Day,Hour/Minute (prev day
at midnight, 2400 at
midnight)
;Output hourly the average reference Temp, TC
Temp, and battery voltage.
07: Average (P71)
1: 3 Reps
2: 1 Loc [ RefTemp ]
;Sample the forward and reflected power.
08: Sample (P70)
1: 2 Reps
2: 1 Loc [ RefTemp ]
;Transfer data to TGT1 every hour.
09: If time is (P92)
1: 0 Minutes into a
2: 60 Minute Interval
3: 30 Then Do
;Transfer data array ID 111 to the TGT1's self-
timed buffer and places the transmitter's latest
forward and reflected power readings into Input
Locations 4 and 5.
10: Data Transfer to GOES (P99)
1: 00 Buffer Selection
2: 4 FWD/Ref Power Loc
[ FwdPwr ]
3: 111 Array ID (ID>0) Transferred
to TGT1'S Buffer
11: End (P95)
;Set Output Flag High (10) for daily output
12: If time is (P92)
1: 0 Minutes into a
2: 1440 Minute Interval
3: 10 Set Output Flag High
;Timestamp data
13: Real Time (P77)
1: 220 Day,Hour/Minute (prev day
at midnight, 2400 at
midnight)
;Designate 222 as the array ID.
14: Set Active Storage Area (P80)
1: 1 Final Storage
2: 222 Array ID or Loc
[ _________ ]
;Average, maximize, and minimize the reference
and TC temperatures, battery voltage, and the
forward and reflected power readings.
15: Average (P71)
1: 5 Reps
2: 1 Loc [ RefTemp ]
16: Maximize (P73)
1: 5 Reps
2: 0 Value Only
3: 1 Loc [ RefTemp ]
17: Minimize (P74)
1: 5 Reps
2: 0 Value Only
3: 1 Loc [ RefTemp ]
;Sends data to the TGT1 once a day. Note: this
is set for 5 minutes after midnight to give ample
Vue de la page 22