Section 7. Installation
255
'10 Minute Data Interval
Scan(10,Min,0,0)
Counter(6) = Counter(6) + 1
Battery(Batt_volt)
PanelTemp(PTemp,250)
TCDiff(Level,1,mV20,1,TypeT,PTemp,True,0,250,1.0,0)
If TimeIntoInterval(0,1,Min) Then
TimeIntoTest = TimeIntoTest + 1
EndIf
'Call Output Tables
CallTable LogTable
NextScan
EndIf
EndProg
7.8.17.5 Scaling Array
CRBasic example Scaling Array (p. 255) demonstrates programming to create and
use a scaling array. Several multipliers and offsets are entered at the beginning of
the program and then utilized by several measurement instructions throughout the
program.
CRBasicExample56. ScalingArray
'Declare viewable variables
Public PTemp_C, Temp_C(10)
Public Count
'Declare scaling arrays as non-viewable variables
Dim Mult(10), Offset(10)
'Declare Output Table
DataTable(min_5,True,-1)
DataInterval(0,5,Min,0)
Average(1,PTemp_C,FP2,0)
Maximum(1,PTemp_C,FP2,0,0)
Minimum(1,PTemp_C,FP2,0,0)
Average(10,Temp_C(),FP2,0)
Minimum(10,Temp_C(1),FP2,0,0)
Maximum(10,Temp_C(1),FP2,0,0)
EndTable